924 HEIDENHAIN Technical Manual iTNC 530 HSCI
MP2195 Handling of status signals from HEIDENHAIN power supply
units
Input: Bit 0 – Status signals that are already active during control
power-up.
0: Missing signals are ignored
1: Missing signals are evaluated
Bit 1– ERR.UZ.GR
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 2 – ERR.TMP
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 3 – Reserved
Bit 4 – ERR.IZ.GR
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 5 – RDY.PS signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 6 – ERR.ILEAK
signal
0: Error message is not suppressed
1: Error message is suppressed
Bit 7 - PF.PS.AC
0: Previous behavior; Error message is not suppressed
1: Error message is suppressed
Bit 8 - PF.PS.DC
0: Previous behavior; Error message is not suppressed
1: Error message is suppressed
MP2195 can also be overwritten by the PLC and the LSV2
protocol.