February 2012 14 – 189
TNCremoNT 8 Start the HEIDENHAIN data transfer program TNCremoNT.
8 Click this icon to open the configuration window.
(Can also be called via Extras / Configuration ... .)
8 Now click on Connection and select Ethernet (TCP/IP).
8 Subsequently, click on Settings and enter the IP address of the control.
8 Check the data transfer mode (BINARY-to-ASCII conversion). It should be set as follows:
8 Confirm with Apply and OK.
8 Click this icon. --> The connection is set up.
8 The TNCremoNT screen is split and the data medium of the control shown in the lower half of the
screen.
If this does not work, check the connecting cable and the settings.
You can also try, whether pinging works --> see next pages!
If the following error message is displayed when the connection is set up, …
... external access to the data medium of the control is not permitted!
In this case press the MOD key and subsequently the EXTERNAL ACCESS ON/OFF soft key in
order to permit access.