4 – 46 HEIDENHAIN Service Manual iTNC 530 HSCI
MC frequency too
high %.2s
The maximum input frequency was exceeded
at an encoder input.
Check encoder signal input frequency.
See ”Further examination of position and
speed encoders” on page 19 – 314.
MC NC
temperature out
of tol.
See "Temperature too high (CPU%1 := %2°C)". See "Temperature too high (CPU%1:= %2 °C)".
%.2s encoder:
amplitude too
large
The amplitude of the encoder signal is too high
or the contamination signal active.
Check the amplitude of the encoder signal.
See ”Position encoders” on page 19 – 277.
%.2s encoder:
amplitude too
small
The amplitude of the encoder signal is too small
or the signal for contamination is active.
Check the amplitude of the encoder signal.
See ”Position encoders” on page 19 – 277.
%.2s measuring
system defective
Contradiction apparent from comparison of
absolute and incremental positions
Inform your service agency.
See ”Encoder interface” on page 19 – 277.
%.2s encoder:
frequency too
high
The maximum input frequency was exceeded
at an encoder input.
Check encoder signal input frequency.
See ”Further examination of position and
speed encoders” on page 19 – 314.
NC: Program
memory erased
After the control was switched on, a file in NC
memory was found faulty and deleted.
Create the file again.
See ”Restoring data” on page 14 – 207.
EMERGENCY
STOP defective
The internal or external EMERGENCY STOP
circuit is found by the system CPU to be
defective.
Check the emergency-stop circuit.
Relays, safety contactor combinations are
defective or too slow.
Input I3 (X42/4) is continuously at 24 V.
MC defective
Check input I3. (See ”"Control is ready" output
and input (EMERGENCY STOP chain)” on page
17 – 228.)
Replace relays, safety contactor combinations.
See ”Error message: EMERGENCY STOP
defective” on page 17 – 230.
Excessive offset
in <axis>
During offset adjustment (with code number or
cyclic) an offset voltage of more than 100 mV
was determined.
Inform your service agency.
See ”Analog speed value interface” on page 21
– 349.
Parallel operation
not possible
You edited the machine or user parameter list
and tried to exit the editor with END. This is not
permitted if the part program or a PLC
positioning operation is running.
Wait until the part program run is ended,
or interrupt the NC program.
PLC: timeout PLC run-time error Edit the PLC program.
See ”PLC main page” on page 11 – 116.
PLC partition: Not
enough memory
Not enough free memory on the PLC partition Inform your service agency.
Delete unneeded files from the PLC partition.
Error message Possible cause of error Measures for error diagnosis and/or
corrective action
Additional information and descriptions
in the manual
Additional information and descriptions
in the manual