29 – 548 HEIDENHAIN Service Manual iTNC 530 HSCI
Setting date and
time on the control
8 Check the date and time of the control and reset it, if necessary.
--> See ”Setting the system time” on page 13 – 173.
Setting up the
data interface
8 Make the settings for Ethernet transmission on the control.
--> See ”Via Ethernet” on page 14 – 183.
8 Or define the settings for the RS 232 interface.
--> See ”Via RS-232-C/V.24 serial interface” on page 14 – 192.
Restoring the data As you could probably not save any data from the defective HDR, you must use available archives
(PLC data, TNC data) to restore the data on the new HDR.
8 Establish a connection between your laptop and the control.
--> See ”Connection setup” on page 14 – 183.
8 Load the correct backup on the new HDR.
--> See ”Restoring data” on page 14 – 207.
Figure: Check marks for LIES_MP.A and READ_MP.A removed
Note
If required, you can obtain PLC and machine data from the machine manufacturer.
Note
In the LST file, delete the blue check marks for the files LIES_MP.A and READ_MP.A.
Background:
The files LIES_MP.A and READ_MP.A that contain the comments (in German and English) to the
current machine parameters belong to every NC software version (can be found under
PLC:\JH\...).
As the replacement SSDRs are normally supplied with the latest NC software version, the
LIES_MP.A/READ_MP.A in your backup file possibly belongs to an older NC software version. If you
have deleted the check marks in your LST file, the current LIES_MP.A/READ_MP.A is not overwritten
by the old LIES_MP.A/READ_MP.A.
It is not recommended to protect the LIES_MP.A and READ_MP.A files on the control as protected
files cannot be updated during an NC software update!