30 – 596 HEIDENHAIN Service Manual iTNC 530
MP2199.x As of CC 424(B): Assignment of the drive to the power supply module
Input: 0: The axis/spindle is assigned to the UV in MP2198.0
1: The axis/spindle is assigned to the UV in MP2198.1
340 490-04
MP2200.x Motor
Input: Name of the selected motor
(is entered by the iTNC)
PLC
RUN
MP2202.x Overwrite “Line count” from the motor table
Input: *: Input from the motor table active
0: No speed encoder (volts-per-hertz control mode)
1 to 999 999
340 420-05
PLC
RUN
MP2204.x Overwrite “Counting direction” from the motor table
Input: *: Input from the motor table active
+: Positive counting direction
–: Negative counting direction
340 420-05
RESET
MP2206.x Overwrite “Type of encoder” from the motor table
Input: *: Input from the motor table active
0: No speed encoder (volts-per-hertz control mode)
1: Incremental rotary encoder with Z1 track
2: Absolute rotary encoder with EnDat interface (aligned)
3: Absolute linear encoder with EnDat interface
4: Linear motor with one reference mark (CC424(B))
5: Absolute rotary encoder with EnDat interface (not aligned)
6: Incremental rotary encoder without Z1 track
7: Incremental rotary encoder with distance-coded reference marks (nonaligned)
8: Incremental linear encoder with distance-coded reference marks (not aligned)
340 420-05
RESET
340 490-03
MP2208.x Inductance of the series reactor
Input: * = Input from the motor table active
Value of the series reactor in [µH]
340 490-03
MP2209.x Mass moment of inertia of a drive motor
Input: * = Input from the motor table active
Value of the mass moment of inertia in [kgm2]
340 490-03
MP2210.x Only CC 424(B): Reduction of the nominal voltage (and, as a result, the nominal
magnetizing current) at the rpm for field weakening during idle running.
Input: 0 to 60 [%]
0 = Function inactive
340 490-01
MP Function and input SW version
and
behavior