EasyManua.ls Logo

HEIDENHAIN MANUALPLUS 620 - Page 193

HEIDENHAIN MANUALPLUS 620
1818 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
January 2012 3.6 Supply Voltages in the HSCI System 193
It is possible to connect both 24 V output voltages of the PSL 13x in parallel.
In this way the PSL supplies only a maximum output power of 750 W, which
fulfills the requirements for PELV according to EN 61800-5-1. However,
because of the parallel circuit, a PSL 130 supplies only an output voltage of
+24 V, which can then be used as desired for the 24 V NC voltage or the
24 V PLC voltage. An additional PSL 13x can be used for the respective other
voltage.
U
Z
DC-link current Since the power to the PSL 130 is supplied through the DC-link, the voltage
fed into the DC-link by the motors that are still running can be used during line
voltage failures. The PSL 130 uses the supply voltage buffered via the DC-link
to maintain the power supply for the control until the non-HEIDENHAIN
inverter system has been shut down properly by the control.
If the PSL is connected over litz wires instead of the DC-link conductor bars, a
wire cross section of at least 1.5 mm
2
must be used. Fuses or a motor protec-
tion switch of 6.3 A or greater for conductor protection must be selected
depending on the wire cross section used. The PSL 130 is protected internally
by a fuse (4 A).
HEIDENHAIN offers insulated conductor bars if you want to position the
PSL 130 next to the left of the UVR inverter and connect it to the DC-link via
conductor bars. Two conductor bars are required for each connection. The
conductor bars are shipped in packaging units. Also, this position makes it pos-
sible to connect the grounding conductor of the PSL via conductor bars. There-
fore, angulated non-insulated conductor bars are also included in this packag-
ing unit. This makes it possible to continue using the straight conductor bar
included with the UVR for the grounding conductor connection from the UVR
to the inverters via the right side.
Danger
When using it to supply the PLC, the common 0 V signal must be con-
nected by a 6 mm
2
conductor to the machine's central ground.
Connecting termi-
nals
Assignment
–U
Z
DC-link voltage –
+U
Z
DC-link voltage +
Length For connection to ID (conductor bar set)
150 mm UVR 120D/130D 687 669-01
200 mm UVR 140D/150D 687 670-01
250 mm UVR 160D/160DW 687 671-01
Note
Tightening torque for the screws of the DC-link conductor bars = 3.5 Nm.

Table of Contents

Other manuals for HEIDENHAIN MANUALPLUS 620

Related product manuals