July 02 Mounting and Electrical Installation TNC 370 D 3–15
3.7.6 Analog Nominal Value Output
Maximum loading of the analog outputs: 2 mA
Maximum capacitance: 2 nF
X8 Nominal Value Output
Logic unit Connecting Cable
D-sub terminal
(female) 15-pin
Assignment D-sub
connector
(male) 15-pin
Color
1 Nominal value output 1 1 BN
2 Analog input 2 BN/GN
3 Nominal value output 2 3 YL
4 Do not use 4 RD/BL
5 Nominal value output 3 5 PK
6 Do not use 6 GY/PK
7 Nominal value output 4 7 RD
8 Nominal value output 5 8 VI
9 0V Nominal value output 1 9 WH
10 0V Analog input 10 WH/GY
11 0V Nominal value output 2 11 GN
12 Do not use 12
13 0V Nominal value output 3 13 GY
14 0V Nominal value output 4 14 BL
15 0V Nominal value output 5 15 BK
Housing External shield Housing External shield
· The connecting cables to the nominal value outputs must not have more than one intermediate
terminal.
· If it is necessary to branch to physically separate servo inputs, the connection must be
made in a grounded terminal box. Suitable terminal boxes are available from HEIDENHAIN
(Id. Nr. 251 249 01).
· The chassis of the terminal box must be electrically connected with frame of the machine.
· The 0 V connection of the nominal-value-difference inputs must be connected with signal
ground. Required cross section ³ Ø 6 mm².
· Use only original HEIDENHAIN connecting cables and connecting elements.