4–64 TNC 370 D Machine Parameters July 02
4.8 Integrated PLC
Machine
parameter
Function and input Change via Reaction
MP4010 PLC program out of EPROM or RAM
Input: 0 or 1
0 = EPROM
1 = RAM
Reset
MP4020 PLC compatibility
Input: %xxxxxxx
Bit 0
0 = non-compatible (marker range 4xxx)
1 = compatible (marker range 2xxx)
Bit 1 to 5 reserved
Bit 6
1 = PLC positions in the format
1/10000 mm; oriented spindle stop
triggered by module 9171 or by marker
M4130/D592 in the format 1/10000°
Reset
MP4060.0-3 Path-dependent lubrication
Input: 0 to 99 999.9999 [mm]
PLC
RUN
MP4070 Compensation per PLC cycle for lag-
tracking error compensation
Input: 0.001 to 0.005 [mm]
PLC
RUN
MP4110.0-47 Time for Timer T0 to T47
Input: 0 to 65 535 [PLC cycles]
PLC
RUN
MP4120.0-31 Preset value for counter C0 to C31
Input: 0 to 65 535 [PLC cycles]
PLC
RUN
MP4130
MP4130.0
MP4130.1
MP4130.2
MP4130.3
MP4130.4
MP4130.5
Number the fast PLC inputs
Input: 0 to 255 [No. of the PLC input]
Fast PLC input for suppressing the
monitoring functions
No function
Fast PLC input sets M4590
(signal duration > 6 ms)
Fast PLC input sets M4591
(signal duration > 6 ms)
Fast PLC input sets M4592
(signal duration > 6 ms)
Fast PLC input sets M4593
(signal duration > 6 ms)