December 2001 Monitoring Functions 6 157
MP1150.1 Time period for which the monitoring function is to remain
off after the fast PLC input defined in MP4130.0 is set
Input: 0 to 65.535 [s]
Recommended: 0.2 to 0.5
MP4130.0 Number of the high-speed PLC input for switching off the
monitoring functions
Input: 0 to 255 [no. of the PLC input]
TNC 426 M, TNC 430 M:
If you use I32, enter the following values:
up to 280 474-11: MP4130.0 = 159
as of 280 474-12: MP4130.0 = 32
as of 280 476-01: MP4130.0 = 32
The inputs of the PL 4xxB may not be used!
MP4131.0 Activation criterion for fast PLC input for switching off the
monitoring functions
Input: 0: Activation at low level
1: Activation at high level
Set Reset
W522 Enabling the fast PLC inputs
Bit 0: Fast PLC input is defined in
MP4130.0 for switching off the
monitoring functions
PLC PLC