AMD – Medium-pressure axial fans
Installation and Operating Instructions
8
In particular, the inlet and outlet opening area must be protected by mounting extension ducts (for horizontal air flow
direction) or e.g. an on-site weather protection cover (end/beginning of a round/rectangular duct section for vertical
air flow direction).
The openings in the fan casing must be protected against the penetration of precipitation by a suitable installation
position (openings on side or below). In this respect, particular attention must be paid to the casing feed-through for
the supply line between the casing terminal box and motor connection.
3.3 Two-stage and parallel units
The various requirements concerning pressure increases, conveying capacities and space requirements are frequently
fulfilled by two-stage Z or parallel P units in the area of Technical Building Equipment (TGA). The Helios range (see sales
documents) offers corresponding mounting kits for the respective construction:
Abmessungen:
3.4 Bearing condition diagnostics
Type: LZD-Basic and LZD-Comfort
The Helios bearing condition diagnostics system serves to securely monitor the functionality of motor bearings in
the drive motor of the smoke extraction fan. The system optionally allows the early detection of imminent bearing
damage by constantly or occasionally monitoring the bearing conditions. The bearings are not replaced periodically,
but depending on the actual wear. In this respect, the test and maintenance plan in these Installation and Operating
Instructions must be observed. Before operation and the use of bearing condition diagnostics, the separate Installation
and Operating Instructions for the monitoring system must be observed.
Information on other accessories can be found on the internet (www.heliosselect.de), TGA catalogue or the Helios
sales documentation.
Fig.11 Fig.12
Terminal box
Terminal box
depending on accessories
MP-Z MP-P
Ø A B C D E A B C D E F G
1)
H I J
315 317 356 381 1080 8x Ø9.5 317 356 381 840 0 487 420-520 1085 316.5 8x Ø9.5
355 357 395 415 1206 8x Ø9.5 357 395 415 903 0 550 460-580 1120 336 8x Ø9.5
400 402 438 471 1266 12x Ø9.5 402 438 471 963 0 579,5 510-580 1120 346.5 12x Ø9.5
450 452 487 519 1416 12x Ø9.5 452 487 519 1038 10 654 560-650 1200 397 12x Ø9.5
500 502 541 570 1416 12x Ø9.5 502 541 570 1038 40 654 615-730 1500 445 12x Ø9.5
560 562 605 636 1960 16x Ø11.5 562 605 636 1310 65 925,5 700-820 1600 477 16x Ø11.5
630 632 674 719 2110 16x Ø11.5 632 674 719 1455 115 990 760-920 1700 527 16x Ø11.5
710 713 751 799 2110 16x Ø11.5 713 751 799 1455 155 980 860-1020 1900 639 16x Ø11.5
800 801 837 897 2010 24x Ø11.5 801 837 897 1425 200 928 950-1120 2000 689 24x Ø11.5
900 902 934 997 2190 24x Ø11.5 902 934 997 1515 250 1018 1070-1240 2200 749 24x Ø11.5
1000 1001 1043 1097 2190 24x Ø11.5 1001 1043 1097 1515 300 1019 1200-1370 2400 814 24x Ø11.5
1120 1128 1174 1216 2460 24x Ø11.5 1128 1174 1216 1650 335 1154 1320-1380 2500 834 24x Ø11.5
Two-stage design / mounting kit MP-Z
Two fans connected in series (Fig.11) ensure the
unrivalled power density and advantageous installa-
tion due to minimum space requirement.
The two fans are arranged in sequence and
connected with extension ducts.
m Vertical mounting ring is not possible (MRV)
Scope of delivery:
- Extension ducts (2 pcs.) incl. mounting kit
(hexagon head screws, nuts, spring washers).
Parallel unit / mounting kit MP-P
Two fans connected in parallel (Fig.12) provide
large air volumes with the corresponding pressure
rate and they meet the requirements for garage
ventilation and smoke extraction in particular.
Two identical fans arranged side by side work in
the same duct system.
Scope of delivery:
- Extension ducts (2 pcs.),
- Backdraught shutters (2 pcs.),
- Mounting brackets (4 pcs.)
- Mounting rails (2 pcs.)
- Mounting kits (hexagon head screws, nuts, spring
washers, washers and threaded plate).