Selecting the steam generator output for the steam room
You can estimate the power requirement using the formula below.
Volume (m
3
) x K1 x K2 = Power requirement (kW)
Forced ventilation K1 = 0.75
No ventilation K1 = 0.52
Acrylic wall K2 = 1.00
Light wall: board + tile K2 = 1.25
Heavy wall: stone, concrete + tile K2 = 1.50
Very heavy wall: stone, concrete + tile K2 = 2.00
In heavy built steam rooms, it is recommended to use e.g. electric heating cable for warming the seats,
walls and floors.
Output Light struc-
ture, acryl-
ic, tem-
pered glass
Light
board
wall
+ tile
Heavy wall,
concrete,
stone
Steam
kg / h
kW No A/C Air condi-
tioned
No A/C Air condi-
tioned
No A/C Air condi-
tioned
3,4 2 – 7 m³ 2 – 6 m³ 2 – 6 m³ 2 – 5 m³ 2 – 5 m³ 2 – 4 m³ 5
4,7 3 – 8 m³ 3 – 7 m³ 3 – 7 m³ 2 – 6 m³ 2 – 6 m³ 2 – 5 m³ 6
6,0 4 – 13 m³ 4 – 9 m³ 4 – 8 m³ 3 – 7 m³ 3 – 7 m³ 3 – 6 m³ 8
7,7 6 – 15 m³ 6 – 11 m³ 6 – 10 m³ 5 – 9 m³ 5 – 9 m³ 4 – 8 m³ 10
9,5 9 – 17 m³ 9 – 13 m³ 9 – 14 m³ 8 – 13 m³ 7 – 11 m 6 – 9 m 13
12,0 12 – 24 m³ 11 – 18 m³ 11 – 20
m³
9 – 16 m³ 9 – 16 m³ 8 – 12 m³ 16
14,0 18 – 30 m³ 14 – 22 m³ 14 – 24
m³
12 – 18 m³ 11 – 17 m³ 10 – 14 m³ 19
Table for selecting a steam generator based on the steam room volume and wall materials.