5
ELECTRICAL CONNECTIONS:
The steam generator is connected (semi-fixed connection) to the mains power, in accordance with
local installation regulations.
Steamer Power 400V/415V 3N 230V/240V 1N 230V3~ Room size
KW Amp Amp Amp m³ *)
HSX 34 3.4 5/5 15/14 8/8 1.5-2.5
HSX 47 4.7 7/6,5 20/19 12/11 2.5-5
HSX 60 6.0 9/8 26/25 15/14 5-7
HSX 77 7.7 12/11 33/32 19/18 7-10
HSX 95 9.5 15/13 24/23 10-12
HSX 120 12.0 19/17 30/29 12-15
HSX 140 14.0 23/21 35/34 15-18
Electrical connections are only to be installed by a licensed electrician.
*) Walls made of heavy materials, such as concrete, brick or stone require a higher output to
generate sufficient heat. Ventilation must also be given extra power.
The required power output can be estimated using the fomula below.
Volume (m3) x K1 x K2 = Required output (kW)
Ventilation K1 = 0.75
No ventilation K1 = 0.52
Acrylic walls K2 = 1.00
Light construction wall: drywall + tile K2 = 1.25
Heavy construction wall: stone, concrete + tile K2 = 1.50
Steam generator 2-phase control: (Not in the special Belgian version)
The steam generator thermal resistors are 2-phase controlled.
Example: The temperature is set for +43 °C. When the temperature reaches +43 °C two resistors
are switched off with a contactor and one remains on to maintain the temperature with a relay on the
circuit board. If the temperature drops 1 °C, all resistors will be switched back on. If the
temperature rises 1 °C, all three resistors will be shut off. This will ensure an even steam output for
the duration of operation.