26 27
In series to
the 24h line
3 Programmation
3.1 Timing
3.1.1 Exiting time regulation
The exiting time allows the system user to leave the protected zones after the system
enabling. During this time a possible activation of the sensors of the all protection zones
doesn’t activate alarms.
This timing is adjustable from 5 to 75 seconds by the trimmer situated inside of the central
unit, near the terminal boards.
The exiting time is signalled by the blinking of the green LED “USCITA” situated on the
front panel of the central unit.
3.1.2 Alarm time regulation
The alarm time is adjustable from 180 seconds to 3 ÷ 10 minutes by the trimmer situated
inside of the central unit, near the terminal boards.
3.1.3 Entering time regulation
In-put time is the time user needs to enter into protected places and to switch off the
system before alarm start. During this time, a possible activation of the sensors on the secured
zone,(zone 1) won't cause alarms.
This timing is adjustable from 5 to 90 sec through the trimmer in the control unit, next to
terminal box.
If the electronic key or any command system are installed out of the protected places is
advisable to regulate to the minimum this timing.
3.2 Exclusion of Internal buzzer
On the circuit of the control unit there is a jumper J1 (TM500P, TM900P, PROTEC9).
J1=OFF Sound signals of the internal buzzer are excluded. (during out/in time and in
alarm condition)
EXIT TIME
ALARM
ENTRY TIME
2.3.4 Sirens
Serie TM / Serie PROTEC burglary central unit - User’s manual Programmation
Self-powered siren
Electronic
siren
J1
EXIT
ENTRY
J1
BUZZER
J1 OFF=BUZZER OFF
J1 ON=BUZZER ON
ALARM
12Vcc Int12V Key Led key
G
Com
zones 24H Z1 Z3 Z4 Z5 Z6 Z7 Z8
NO
NCC
Alarm
Z2
R
Sir
S.A.
+ +++
TM500P
TM900P
PROTEC9
TAMPER
+
12V
TAMPER
+
12V
Sir
S.A.
12Vcc Int12V Chiave Led
V
Com
zone 24H Z1 Z3 Z4 Z5 Z6 Z7 Z8
NA
NCC
Allarme
+
Z2
+
R
++
TM500P
TM900P
PROTEC9
security security