Switching
[ Switching > L2-Redundancy > MRP ]
200
RM GUI GRS
Release
8.0
09/2019
Possible values:
forwarding
The port is enabled, connection exists.
blocked
The port is blocked, connection exists.
disabled
The port is disabled.
not-connected
No connection exists.
Fixed backup
Activates/deactivates the backup port function for the
Ring port 2
.
Note: The switch over to the primary port can exceed the maximum ring recovery time.
Possible values:
marked
The
Ring port 2
backup function is active. When the ring is closed, the ring manager reverts back
to the primary ring port.
unmarked
(default setting)
The
Ring port 2
backup function is inactive. When the ring is closed, the ring manager continues
to send data on the secondary ring port.
Configuration
Ring manager
Enables/disables the
Ring manager
function.
If there is one device at each end of the line, then you activate this function.
Possible values:
On
The
Ring manager
function is enabled.
The device operates as a ring manager.
Off
(default setting)
The
Ring manager
function is disabled.
The device operates as a ring client.
Advanced mode
Activates/deactivates the advanced mode for fast recovery times.
Possible values:
marked
(default setting)
Advanced mode active.
MRP-capable Hirschmann devices support this mode.
unmarked
Advanced mode inactive.
Select this setting if another device in the ring does not support this mode.