Diagnostics
[ Diagnostics > Status Configuration > Security Status ]
242
RM GUI GRS
Release
8.0
09/2019
Possible values:
marked
(default setting)
Monitoring is active.
If the settings allow the device to load an unencrypted configuration profile from the external
memory, then in the
Security status
frame, the value changes to
error
.
If the following preconditions are fulfilled, then the
Security status
frame in the
Basic Settings >
System dialog, displays an alarm.
The configuration profile stored in the external memory is unencrypted.
and
The
Config priority
column in the
Basic Settings > External Memory
dialog has the value
first
.
unmarked
Monitoring is inactive.
Link interrupted on enabled device ports
Activates/deactivates the monitoring of the link on the active ports.
Possible values:
marked
Monitoring is active.
If the link interrupts on an active port, then in the
Security status
frame, the value changes to
error
. In the
Port
tab, you have the option of selecting the ports to be monitored individually.
unmarked
(default setting)
Monitoring is inactive.
Access with HiDiscovery possible
Activates/deactivates the monitoring of the HiDiscovery function.
Possible values:
marked
(default setting)
Monitoring is active.
If you enable the HiDiscovery function, then in the
Security status
frame, the value changes to
error
.
unmarked
Monitoring is inactive.
You enable/disable the HiDiscovery function in the
Basic Settings > Network
dialog.
IEC61850-MMS active
Activates/deactivates the monitoring of the
IEC61850-MMS
function.
Possible values:
marked
(default setting)
Monitoring is active.
If you enable the
IEC61850-MMS
function, then in the
Security status
frame, the value changes to
error
.
unmarked
Monitoring is inactive.
You enable/disable the
IEC61850-MMS
function in the
Industrial Protocols > IEC61850-MMS
dialog,
Operation