Installation OZD Profi 12M ...
Release
01
07/2017
59
EMC and immunity
Power consumption/power output
Transmission distance:
Fiber 10/125 - 15000 m
Fiber 50/125 (default) - 3000 m 10000 m
Fiber 62.5/125 (default) - 3000 m 10000 m
Fiber 200/230/125 (default) 400 m - -
Fiber 200/230/125 (reduced) - 800 m (12 MBit/s)
1000 m
(<12 MBit/s)
-
Fiber 980/1000 (default) 80 m - -
Fiber 980/1000 (reduced) 57 m - -
a. The specified transmission distance must not be exceeded regardless of the maximum
allowed attenuation line.
EMC interference emission
Radiated emission
EN 55022 Class A
EN 55032 Class A
FCC 47 CFR Part 15 Class A
EMC interference immunity
Electrostatic discharge
EN 61000-4-2
IEEE C37.90.3
Contact discharge ± 4 kV
EN 61000-4-2
IEEE C37.90.3
Air discharge ± 8 kV
Electromagnetic field
EN 61000-4-3 80 MHz ... 1000 MHz 10 V/m
1400 MHz ... 2000 MHz
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
DC supply connection ± 2 kV
EN 61000-4-4
IEEE C37.90.1
Data line ± 1 kV
Voltage surges - data line
EN 61000-4-5 line/ground ± 1 kV
Conducted disturbances
EN 61000-4-6 150 kHz ... 80 MHz 10 V
Device name Maximum power consumption Maximum power output
OZD Profi 12M ... 3.9 W (1 electrical port) 13.3 BTU (IT)/h
4.7 W (2 electrical ports) 16 BTU (IT)/h
Transmission distance
a
P G G-1300