Two wrenches required to prevent
damaging the copper piping.
Apply Refrigerant Oil.
CautionsforPipingConnectionWork
(a) Connecttheindoor/outdoorconnecting
pipes.Securethepipesanddonottouch
otherobjects,suchasceilingsforexample.
(Otherwise,abnormalsoundmaybeheard
duetothevibrationofthepiping.)
(b) Applyrefrigerantoilslightlyonthesheet
surfaceofthepipeandarenutbeforethe
aringwork.Thentightenthearenutwith
thespeciedtighteningtorqueusingtwo
wrenches.Alwaysuseaback-upwrenchto
preventtwistingofthecopperpipingwithin
theunitassembly.Performthearingwork
ontheliquidpipingsidebeforethegas
pipingside.Checkthegasleakageafterthe
aringwork.
NOTE:
Refrigerantoiliseld-supplied.
[EtherealOilFVC50K,FVC68D(Idemitsu
KousanCo.Ltd.)]
(c) Whentemperatureandhumidityinsidethe
ceilingexceed27
o
C(80
o
F)/RH,relative
humidity,80%,applyadditionalinsulation
approximately20mm(13/16inch)thickness
totheaccessoryinsulation.Itprevents
condensationonthesurfaceoftheinsulation
(refrigerantpipeonly)andpossibledamage
toelectroniccomponents.
(d) Performtheair-tightleakagetest4.15MPa
(601psi)forthetestpressure.Refertothe
TechnicalManualfortheOutdoorUnitfor
moredetails.
(e) Performcoldinsulationworkbyinsulating
andtapingtheareconnectionandreducer
connection.Alsoinsulatealltherefrigerant
pipes.
Do not apply excessive force to the are
nut when tightening. Excessive force can
result in the are nut cracking and refrigerant
leakage may occur. Use the specied
tightening torque.
For more details of the refrigerant piping
work, vacuum pumping and refrigerant
charge, refer to the Technical Manual for the
Outdoor Unit.
RequiredTighteningTorque
PipeSize TighteningTorque
6.35mm (ɸ1/4inch)
9.52mm (ɸ3/8inch)
12.7mm (ɸ1/2inch)
15.88mm (ɸ5/8inch)
19.05mm (ɸ3/4inch)
14to18 N
m (10.3to13.3 ft
.
lbs)
34to42 N
m (25.1to31.0 ft
.
lbs)
49to61 N
m (36.1to45.0 ft
.
lbs)
68to82 N
m (50.2to60.5 ft
.
lbs)
100to120 N
m (73.8to88.5 ft
.
lbs)