6. Electrical Wiring
LOCK ALL ELECTRICAL POWER SUPPLY SWITCHES IN THE OFF POSITION BEFORE INSTALLING
THE UNIT. FAILURE TO DISCONNECT POWER SUPPLY MAY RESULT IN ELECTRICAL SHOCK OR
EVEN DEATH.
Turn off the main power switch to the Switch Box, the indoor unit and the outdoor unit before
electrical wiring work or a periodical check is performed.
Insulate electrical wiring, condensate piping, and electrical components from threats posed by
burrowing animals and temperature extremes. Failure to do so can over time, deteriorate system
performance.
Secure the cables. External forces on the terminals could lead to a re.
Tighten screws according to the following torque.
M4: 1.0 to 1.3 N
m (0.7 to 1.0 ft
.
lbs) (TB1, TB2)
Wrap the eld-supplied insulation around the wires, and plug the wiring connection hole with the
seal material to protect the product from any condensate water or insects.
Tightly secure the wires with the cable clamp inside the Switch Box.
Do not connect the ground wiring to the gas pipe, condensate pipe or lightening conductor.
Gas pipe: An explosion and ignition may occur when gas leaks.
Water pipe: There is no effect of ground wiring when a hard vinyl pipe is used.
Lightning conductor: The ground electric potential abnormally increases when a lightning
conductor is used.
6.1GeneralCheck
(1) Makesurethatthefield-selected electricalcomponents(mainswitches,fuses,ELB(EarthLeakage
Breaker),wires,conduitconnectorsandwireterminals)areproperlyselectedaccordingtothe
electricaldataindicatedinTable6.1.MakesurethatthecomponentscomplywithNationalElectrical
Code(NEC).
(2) Communicationcablemustbeaminimumof18-Gauge,2-Conductor,StrandedCopper.Shielded
cablemustbeconsideredforapplicationsandroutinginareasofhighEMIandothersourcesof
potentiallyexcessiveelectricalnoisetoreducethepotentialforcommunicationerrors.Whenshielded
cablingisapplied,properbondingandterminationofthecableshieldisrequiredasperHITACHI
guidelines.Plenumandriserratingsforcommunicationcablesmustbeconsideredperapplication
andlocalcoderequirements.
(3) Useshieldedcommunicationcableforcommunicationcablebetweentheindoorandtheoutdoorunit
(Max.1,000m(3,281ft)),andconnecttheshieldedparttothegroundscrewintheelectricalbox.
(4) Makesurethatthepowersupplyvoltageiswithin±10%oftheratedvoltage.
(5) Checkthecapacityoftheelectricalwiring.Ifthepowersupplycapacityistoolow,thesystemcannot
bestartedduetothevoltagedrop.
(6) Makesurethatthegroundwiringisconnected.