Item Description
Power rating of
chassis
Shows the total rated power of modules in the
server chassis.
Power capping DCMI mode Shows the condition of DCMI mode.Action
combo box on the upper right. Enable/disable
the DCMI mode from Action menu.
Accurate power
control value (APC)
(Setting)
Shows the APC (accurate power control) power
capping value in operation.
Nothing is shown if DCMI mode enabled.
Emergency power
control value (EPC)
Shows the EPC (emergency power control)
power capping value for protecting the
equipment.
Control status
(APC)
Shows whether or not the performance is
limited due to exceeding the APC setting value.
Control status
(EPC)
Shows whether or not the performance is
limited due to exceeding EPC.
Nothing is shown if DCMI mode enabled.
Power supply module redundancy Shows the power supply module redundancy.
One of the following is shown depending on the
equipment power voltage:
100VAC: N+N, N+1, N+0
200VAC – 240VAC: N+N, N+1
Power supply module optimization Enables or Disables power supply module
optimization.
Power equipment
environment
Enable/Disable Shows the power equipment environment
setting to EPC is either Enable no Disable.
Rated current of
circuit breaker
Sets the rated current of a fuse free breaker
(FFB).
100VAC: 10A – 100A (default value: 15A)
200VAC – 240VAC: 15A – 100A
With the number of PDU 0, default value is 15A.
With the number of PDU 1, default value is 30A.
Number of circuit
breaker
Sets the number of fuse free breakers (FFB):
1/2/3/4:
With N+N, default value is 2.
With N+1, default value is 1.
With N+0, default value is 1.
Rated current of
PDU
Sets the PDU rated current.
100VAC: Not supported.
200VAC – 240VAC: 15A – 100A (default value:
24A)
Number of PDU Sets the number of PDUs: 0/1/2
With N+N, default value is 2.
With N+1, default value is 1.
Operating the Web Console
2-163