Chapter 3 Programming
3 – 69
MV_PLS_Start
This function block is to output pulse train for position control. Pulse train stops after specified number
of pulses have been completed.
A rising edge starts the execution.
0: Without ramp
1: With ramp
Frequency of pulse train outputs (20 to 100,000 [Hz])
The number of pulses
0 to 4,294,967,295 (direction disabled)
-2,147,483,648 to 2,147,483,647 (direction enabled)
Initial frequency (20 to 65,535[Hz])
If ramp is not used (xMode=0),
set 0 or leave as no connection.
Acceleration ratio (1 to 65,535 [Hz/100ms])
Deceleration ratio (1 to 65,535 [Hz/100ms])
Execution done successfully
Note: If this function block is executed while pulse train output in operation, all the parameters are overwritten.
dwPulses
= area
= distance
dwPulses
= area
= distance
dwFrequency [Hz] wInitial_FQ [Hz]
dwFrequency [Hz] wInitial_FQ [Hz]