Floor
LoadRating
(kg/m2)
Required Clearance (a+b) m
c= -0.3 c=0 c=0.2 c=0.4 c=0.6 c=0.8 c=1.0 c=1.4
400 4.0 3,2 2.7 2.3 2.0 1.7 1.4 1.0
350 5.6 4.6 4.0 3.5 3.1 2.7 2.4 1.9
300 8.0 6.7 6.0 5.4 4.9 4.4 4.0 3.3
Notes;
1. Actual clear
ances for installation should be determined after consulting with the
construction specialist r
esponsible for installations in the building. Clear
ances can
vary depending on the size/layout of the system and building conditions.
2. When various congurations of stor
age systems are arranged in a row, clearance
values based on the largest storage system conguration should be used.
3. For easier maintenance operations, make clearance (c) as large as possible.
Seven-rack conguration
Chapter 4: Site preparation specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 103