Figure 37 Example of a separated racks in a dual controller conguration
Additional guidelines
■
You can implement extended cabling with a system installed in customer-supplied
racks only if the r
acks meet HDS specications and are approved by the HDS
Customer Sales and Support (CSS) organization.
■
The high temperature mode option can be implemented on VSP G1x00 systems using
extended cabling.
■
The minimum microcode requirements to support extended cabling includes:
●
VSP G1000: V02 (microcode 80-02-01-00/01), released in October 2014, must be
installed to support the SAS optical cables
●
VSP G1500: SVOS 7.0 (microcode 80-05-01-00/00), released in October 2016, must
be installed to support the SAS optical cables
●
To maintain proper functioning of storage system, continue to keep the storage
system microcode level current to ensure code enhancements and xes. If the
storage system is using an earlier version of microcode, contact an authorized
service provider for assistance with planning, ordering, and installing a more
current microcode version.
■
Consult a Hitachi Vantara representative for more information about system
congurations and available extended cabling options.
Extended cable connections