EasyManua.ls Logo

Hitachi G1500 - Appendix C: Electrical Specifications; Input Power Specifications

Hitachi G1500
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix C: Electrical specifications
The VSP G1000, VSP G1500, and VSP F1500 storage system PDUs support both single-
phase or three-phase AC power. The system components use single phase 220 VAC.
Table 34 Input power specications
Item
Input Power to
PDUs
Input
Current
1
Steady
Current
2
Leakag
e
Current
Inrush Current
1st (0-
p)
2nd (0-
p)
1st (0-p)
Time
(-25%)
DKC PS Single phase,
2 pole + gr
ound
A
C 200 V -8%
min to
A
C 240 V +6%
max
3
7.18A
3.59A 0.28mA 20A 15A 80ms
UBX PS 2.07A 1.04A 1.75mA 25A 20A 150ms
SBX PS 2.61A 1.31A 1.75mA 25A 20A 150ms
FBX PS 2.83A 1.42A 2.8mA 20A 10A 80ms
Notes:
1. The maximum current in case AC input is not a redundant conguration (in case
of 184 V [200 V - 8%]).
2. The maximum current in case AC input is a redundant conguration (in case of
184 V [200 V - 8%]).
3. 110/120 VAC system is not supported.
Power Supply Locations
The follo
wing gure sho
ws the locations of the po
wer supplies in a contr
oller chassis,
LFF/SFF drive chassis, and FMD chassis.
Appendix C: Electrical specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 140

Table of Contents

Related product manuals