Appendix C: Electrical specifications
The VSP G1000, VSP G1500, and VSP F1500 storage system PDUs support both single-
phase or three-phase AC power. The system components use single phase 220 VAC.
Table 34 Input power specications
Item
Input Power to
PDUs
Input
Current
1
Steady
Current
2
Leakag
e
Current
Inrush Current
1st (0-
p)
2nd (0-
p)
1st (0-p)
Time
(-25%)
DKC PS Single phase,
2 pole + gr
ound
A
C 200 V -8%
min to
A
C 240 V +6%
max
3
7.18A
3.59A 0.28mA 20A 15A 80ms
UBX PS 2.07A 1.04A 1.75mA 25A 20A 150ms
SBX PS 2.61A 1.31A 1.75mA 25A 20A 150ms
FBX PS 2.83A 1.42A 2.8mA 20A 10A 80ms
Notes:
1. The maximum current in case AC input is not a redundant conguration (in case
of 184 V [200 V - 8%]).
2. The maximum current in case AC input is a redundant conguration (in case of
184 V [200 V - 8%]).
3. 110/120 VAC system is not supported.
Power Supply Locations
The follo
wing gure sho
ws the locations of the po
wer supplies in a contr
oller chassis,
LFF/SFF drive chassis, and FMD chassis.
Appendix C: Electrical specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 140