Appendix F: Power distribution units for Hitachi
Universal V2 Rack
The Hitachi Universal V2 Rack is equipped with specic power distribution units (PDU) for
Americas, AP
A
C, and EMEA r
egions. The PDUs can pr
ovide electrical power to the storage
system in a single-phase or three-phase conguration.
Caution:
Befor
e installing thir
d-party de
vices into the r
ack, check the electrical
current draw of each device. Verify the electrical specications and
allowable current load on each PDU before plugging the device into the
PDU.
Balance the electrical current load between available PDUs.
Americas single-phase PDU 1P30A-8C13-3C19UL.P
The follo
wing gure and table describes the specications of the PDU
.
Figure 40 Americas PDU for the Hitachi Universal V2 Rack (Single-phase PDU
1P30A-8C13-3C19UL.P)
Part Number Region Phase Description
1P30A-8C13-3C19U
L.P
Americas Single
208V, 30A (24A
rated) 60Hz
8 IEC C13 + 3 IEC
C19 sockets
NEMA L6-30P
input po
wer plug
4.5 m (14.76
feet) cable
Appendix F: Power distribution units for Hitachi Universal V2 Rack
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 153