Figure 15 Service clearances for a two-rack, dual-controller system
Table 18 Floor load rating and required clearances for a two-rack conguration
Floor load
rating (kg/m2)
Required clearance (a+b) m
c= -0.3 c20 c=0.2 c=0.4 c=0.6 c=0.8 c=1.0 c=1.4
Over 700 0 0 0 0 0 0 0 0
600 0.2 0 0 0 0 0 0 0
500 0.6 0.4 0.2 0.1 0.1 0 0 0
450 0.8 0.6 0.5 0.4 0.3 0.2 0.1 0
Two-rack, dual-controller conguration
Chapter 4: Site preparation specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 88