Figure 17 Service clearances for a three-rack, dual-controller system
Table 20 Floor load rating and required clearances for a three-rack, dual-controller
conguration
Floor Load
Rating
(kg/m2)
Required Clearance (a+b) m
c= -0.3 c=0 c=0.2 c=0.4 c=0.6 c=0.8 c=1.0 c=1.4
Over 700 0 0 0 0 0 0 0 0
600 0.2 0 0 0 0 0 0 0
500 0.7 0.4 0.2 0.1 0 0 0 0
450 1.1 0.7 0.5 0.4 0.2 0.1 0 0
400 1.6 1.2 1.0 0.8 0.6 0.5 0.3 0.1
Three-rack, dual-controller conguration
Chapter 4: Site preparation specications
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide 92