EasyManua.ls Logo

Hitachi G200 - Appendix I: Power Distribution Units for Hitachi Universal V2 Rack; Americas Single-Phase PDU 1 P30 A-8 C13-3 C19 UL.P

Hitachi G200
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix I: Power distribution units for Hitachi
Universal V2 Rack
The Hitachi Universal V2 Rack is equipped with speciî ´c power distribution units (PDU) for
Americas, APAC, and EMEA regions. The PDUs can provide electrical power to the storage
system in a single-phase or three-phase conî ´guration.
Caution:
â– 
Befor
e installing third-party devices into the rack, check the electrical
current draw of each device. Verify the electrical speciî ´cations and
allowable current load on each PDU before plugging the device into the
PDU.
â– 
Balance the electrical current load between available PDUs.
Americas single-phase PDU 1P30A-8C13-3C19UL.P
The follo
wing î ´gure and table describes the speciî ´cations of the PDU.
Figure 1 Americas PDU for the Hitachi Universal V2 Rack (Single-phase PDU
1P30A-8C13-3C19UL.P)
Part Number Region Phase Description
1P30A-8C13-3C19U
L.P
Americas Single
â– 
208V
, 30A (24A
rated) 60Hz
â– 
8 IEC C13 + 3 IEC
C19 sockets
â– 
NEMA L6-30P
input power plug
â– 
4.5 m (14.76
feet) cable
Appendix I: Power distribution units for Hitachi Universal V2 Rack
Hitachi Virtual Storage Platform G200 Hardware Reference Guide 129