Item Controller Drive tray
FMD drive tray: 520/490 or
less
Dense intermix drive tr
ay:
1200/1160 or less
Power consumption (VA/W) CBLH: 840/780 or less SFF drive tray: 320/310 or
less
LFF drive tray: 280/260 or
less
FMD drive tray: 440/420 or
less
Dense intermix drive tray:
1000/960 or less
Notes:
1. The power current of Nx2 described in this table is required for a single power
unit.
2. If one power unit fails, another power unit requires electric current for the two
power units. Therefore, plan the power supply facility so that the current-carrying
capacity for one power unit can provide the total capacity for two power units.
3. This table shows the power requirement (100 V or 200 V) for the maximum
conguration . The actual required power might exceed the value shown in the
table when the tolerance is included.
Electrical specications
Appendix B: Electrical specications for VSP G800
Hitachi Virtual Storage Platform G800 Hardware Reference Guide 74