Hitachi Advanced Server HA820 G2 User Guide 124
•
The components included with the hardware option kit
•
T-30 Torx screwdriver
Procedure
1.
Observe the following alerts.
CAUTION:
The processor assembly must be removed and replaced as a unit. Do not remove the processor from the
carrier.
CAUTION:
When handling the heatsink, always hold it along the top and bottom of the fins. Holding it from the sides
can damage the fins.
CAUTION: THE CONTACTS
ARE
VERY FRAGILE AND EASILY DAMAGED.
To avoid damage to the socket or
processor, do not touch the contacts.
2.
Power down the server.
3.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
4.
Do one of the following:
a.
Extending the server from the rack.
b.
Removing the server from the rack.
5.
Remove the access panel.
6.
Observe the following cautions.
CAUTION:
Be sure to loosen each heatsink nut in the order indicated. Otherwise, damage might occur to the heatsink
or processor.
CAUTION:
Install the processor heatsink assembly as soon as possible after removing it. Do not leave the processor
socket unpopulated for extended periods of time.