P5417086
19
NOTES:
1. After at least three minutes from power ON, change the optional setting.
2. When changing the “CF” setting (change of louver swing angle), restore the power supply or allow the louver to
make one complete swing fully in the auto-swing mode to apply the optional setting.
3. The optional settings may be different according to the indoor and outdoor unit models.
Check to ensure that the unit has the optional setting.
4. Record the setting conditions for each optional setting in the "Setting" column of the table.
5. The above optional functions marked with an “X” at the individual setting can change the condition only when “All
Rooms” is set.
● Table B: Input and Output Number Display and Connectors
● Table C: Input and Output Settings and Display Codes
Input Number Display
Port
Factory Setting
Setting
Input/Output Indication Setting Item Indication
Input 1 CN3 1-2 Remote ON/OFF 1 (Level) 03
Input 2 CN3 2-3 Prohibiting Remote Control after Manual Stoppage 06
Output 1 CN7 1-2 Operation 01
Output 2 CN7 1-3 Alarm 02
Output 3 CN8 1-2 Thermo-ON for Heating 06
NOTES:
* Change the optional setting after waiting at least three minutes elapsed time after start-up.
* Do not set the elevating grille for the total heat exchanger.
* Record the setting conditions for each input and output in the “Setting” column of the table.
Code Indicated Input Output
00 Not set Not set
01 Room Thermostat (for Cooling) Operation
02 Room Thermostat (for Heating) Alarm
03 Remote ON/OFF 1 (Level) Cooling
04 Remote ON/OFF 2 (Operation) Thermo-ON for Cooling
05 Remote ON/OFF 2 (Stoppage) Heating
06 Forbidding Remote Control after Manual Stoppage Thermo-ON for Heating
07 Remote Cooling / Heating Change Total Heat Exchanger
09 Setback Operation