EN
3 ELECTRICAL WIRING
! DANGER
Always make sure to turn o the power of the indoor unit when performing electrical wiring work.
Performing electrical wiring work with the power turned on can damage the circuit boards of the
indoor unit and the remote control switch.
Wiring Example:
AB
AA
BB
Remote
control switch
Remote control
switch (Subsidiary)
Electrical box of
indoor unit
Max. 16 Indoor units
Electrical box of
indoor unit
Terminal board Terminal board
M3.5
screws
M3
screws
M3.5
screws
Use 0.75mm
2
cable, 2-Conductor, Stranded Copper
? NOTE
• Communicationcablingmustbeaminimum0.75mm
2
,2-Conductor,StrandedCopper.Shieldedcable
mustbeconsidered forapplicationsandroutinginareasofhighelectronicinterference(EMI)and
othersourcesofpotentiallyexcessiveelectricalnoisetoreducethepotentialforcommunicationerrors.
Whenshieldedcablingisapplied,properbondingandterminationofthecableshieldisrequiredas
perJohnsonControls-HitachiAirConditioningguidelines.Plenumandriserratingsforcommunication
cablesmustbeconsideredperapplicationandlocalcoderequirements.Theuseofanyothergrade
ofcableotherthanthatspeciedabovecanresultindamagefromEMI.
• Keepaclearanceofmorethan30cmbetweenthetransmissionline(remotecontrolswitchcable
andtransmissionwires)andthepowersourceofindoorunits.Otherwise,theair-conditionermaynot
operateproperlyormalfunctionmayoccurduetotheeectofpowersourcenoise.
• Refertothedocumentationprovidedwitheachunitwhenperformingelectricalwiringworkbetween
theremotecontrolswitchandindoorunits,forthepropersettingofrefrigerantcyclenumberandindoor
unitaddress.
• Nogapshallexistbetweentheremotecontrolswitchcableandtheholeoftheremotecontrolswitch
case.Ifthereisagap,coverthegapwithvinyltape.Otherwise,malfunctionmayoccurduetothe
entranceofwaterdropletsorinsects.
• Incaseofoperatingwithtworemotecontrolswitches(MainandSub),setthemainandsubremote
controlswitchesbyselectingtheappropriatefunctionwiththeremotecontrolswitchesfollowingthe
contentsofFunctionselectionandsettingchapter.Uponcompletionofsettings,turnothepower
supplyofalltheindoorunitconnectedtotheremotecontrolswitches.
Electrical Wiring
PMML0564 rev.1 - 09/2021
3