6. Function Selection
16
A16381H9HF
No. Item Optional Function
Individual
Setting
Setting
Condition
Contents Setting
126 q8 Not used -
00
01
00
01
127 q9 Not used -
00
01
00
01
128 qA Not used -
00
01
00
01
129 qb Operation mode with Setback ×
00
01
02
03
Unavailable
COOL only
HEAT only
COOL & HEAT
130 qC
Temp. dierential for the Setback
operation
×
00
01
02
03
04
2.0°C(3°F)
3.0°C(5°F)
4.0°C(7°F)
5.0°C(9°F)
1.0°C (2°F)
131 qd Minimum stop time of Setback ×
00
01
02
03
04
05
06
07
08
09
10
11
10 min.
20 min.
30 min.
40 min.
50 min.
60 min.
70 min.
80 min.
90 min.
100 min.
110 min.
120 min.
132 qE Setback Mode ×
00
01
02
03
Always
Input
Schedule
Manual
133 qF
Operation state aer Setback
operation ends
×
00
01
02
Stop
Run
State before Setback Operation
134 r1 Dual Setpoint ×
00
01
Unavailable
Available
135 r2
Dierential temp. setting for
Cooling-Heating changeover
×
00
01
02
03
04
05
1.0°C (2°F)(Default)
1.5°C (3°F)
2.0°C (3°F)
2.5°C (4°F)
3.0°C (5°F)
0.5°C (1°F)
136 r3
Setback Temperature
Compensation
×
05
10
15
20
25
30
35
40
45
50
55
0.5°C (1°F)
1.0°C (2°F)
1.5°C (3°F)
2.0°C (3°F)
2.5°C (4°F)
3.0°C (5°F)
3.5°C (6°F)
4.0°C (7°F)
4.5°C (8°F)
5.0°C (9°F)
5.5°C (10°F)
137 r4 Enable/Disable Auto-FrostWash 2 -
00
01
Available
Unavailable
138 r5 Not used -
00
01
00
01
139 r6 FrostWash Manual Setting ×
00
01
Allow
Prohibit
140 r7 FrostWash Automatic Setting ×
00
01
Allow
Prohibit
141 r8 Enable/Disable Auto-FrostWash ×
00
01
Disable
Enable
142 r9
Remote control prohibition during
Setback operation
×
00
01
02
Run/Stop allowed
Run & Stop not allowed (not advised for safety reasons)
Only stop allowed