Table A Optional Setting Items for Function Selection
Items Optional Function Individual setting Setting condition Contents
b1
Cancellation of heating temperature
compensation due to uneven heat load
○
00
01
02
Standard +4ºC
Removal (oset elimination)
Set temperature +2
o
C (*1)
b2 Circulator function at heating Thermo-OFF ○
00
01
Not available
Available
b3
Enforced 3 Minutes minimum operation
time of compressor
○
00
01
Not available
Available
b4 Change of lter cleaning time ○
00
01
02
03
04
Standard
100 hrs
1,200 hrs
2,500 hrs
No indication
b5 Fixing of operation mode ×
00
01
Standard
Fixed
b6 Fixing of setting temperature ×
00
01
Standard
Fixed
b7
Fixing of operation as exclusive cooling
unit
×
00
01
Standard
Fixed
b8 Automatic COOL/HEAT operation ×
00
01
Not available
Available
b9 Fixing of fan speed ×
00
01
Standard
Fixed
bA Not prepared × - Not used
bb
Cooling temperature compensation due to
uneven heat load
×
00
01
02
Standard (No Compensation)
Set Temp. –1
o
C
Set Temp. –2
o
C
bC Not prepared - - Not used (Use as 00 conditions)
bd Not prepared - - Not used (Use as 00 conditions)
bE Not prepared - - Not used (Use as 00 conditions)
C1 Not prepared - - Not used (Use as 00 conditions)
C2 Not prepared - - Not used
C3 HA function (only for Japanese market) ○
00
01
Not available (Use as 00 conditions)
Available
C4 Drain Pump Operation at Heating ○
00
01
Not available
Available
C5
Hi speed
(Except for Hi Speed at Heating Thermo-
OFF)
○
00
01
02
Not available
Hi Speed 1 (*2)
Hi Speed 2
C6 Hi speed at heating Thermo-OFF ○
00
01
Not available
Available
C7
Canceling of enforced 3 minutes minimum
operation time of compressor
○
00
01
Standard
Cancellation
C8 Thermistor of remote control switch ○
00
01
02
Not available
Control by thermistor of remote control switch
Control by average value of indoor suction
thermistor and thermistor of remote control switch
C9 Not prepared - - Not used
CA Not prepared - - Not used
Cb Selection of forced stoppage logic ×
00
01
Forced stoppage input: A Contact
Forced stoppage input: B Contact
CC Not prepared × - Not used (Use as 00 conditions)
Cd Not prepared - - Not used (Use as 00 conditions)
CE Not prepared - - Not used (Use as 00 conditions)
CF Change of louver swing angle ○
00
01
02
Standard (7-Step Operation)
Cold draft prevention
(5 Steps: lower 2 steps cut o)
High ceiling (5 Steps: upper 2 steps cut o)
FUNCTION SELECTION AND SETTING