< Other settings >
10 Select the target of External Input Control.(All Groups/Block/Group).
* Tap the button of a Group to switch its selection state.
* Tap the button of a Block to switch the selection state of all the Groups in the Block.
* Tap the “Select All Groups” button to switch the selection state of all the Groups.
* The selected groups are indicated with a check mark.
11 Tap “Setting completed” to conrm the set contents and return to the External Input/Output Setting screen .
(10) (11)
External Output Setting
1 Select “External Input/Output Setting” on the Service Menu screen.
* Selection is not possible when air conditioners are in operation, or when the contact for external input signal is ON.
(1)
(2)
2 Select the Output target of the External Output (Output 1, Output 2).
3 Select the function to be used with the external output.
* The button for the selected function is highlighted in yellow.
(3)
(4)
4 Tap “Service Menu” to complete the external Input/Output Setting and return to Service Menu screen.
5 Centralised remote controls
PSC-A32MN
TCGB0106 rev.0 - 12/2014
359