20
INSTALLATION MANUAL
7.1. TABLE A OPTIONAL SETTING ITEMS
No. Items Optional Function
Individual
Setting
Setting
Condition
Contents
1b1
Removal of Heating
Temperature
Compensation
○
00
01
02
Standard (Set Temp.
+4ºC)
Removal (Set Temp.)
Set Temp. +2ºC (*1)
2b2
Circulator Function
at Heating Thermo-
OFF
○
00
01
Not Available
Available
3b3
3 Minutes OFF
Guard Compressor
○
00
01
Not Available
Available
4 b4 Period for Filter Sign
○
00
01
02
03
04
Standard
100 hours
1,200 hours
2,500 hours
No Indication
5b5
Fixing of Operation
Mode
×
00
01
Not Available
Available
6b6
Fixing of Setting
Temperature
×
00
01
Not Available
Available
7b7
Fixing Cooling
Operation
×
00
01
Not Available
Available
8b8
Automatic COOL/
HEAT Operation
×
00
01
Not Available
Available
9 b9 Fixing Fan Speed
×
00
01
Not Available
Available
10 bA Not Prepared
×
“- -” Fixed Not Used
11 bb
Cooling Temperature
Compensation
○
00
01
02
Standard (No
Compensation)
Set Temp. –1ºC
Set Temp. –2ºC
12 bC Not Prepared
-
00
01
Not Used
(Use as 00 conditions)
13 bd Not Prepared
-
00
01
Not Used
(Use as 00 conditions)
14 bE Not Prepared
-
00
01
Not Used
(Use as 00 conditions)
15 C1 Not Prepared
-
00
01
Not Used
(Use as 00 conditions)
16 C2 Not Prepared
-
“- -” Fixed Not Used
17 C3 Not Prepared
○
00
01
Not Used
(Use as 00 conditions)
18 C4 Not Prepared
○
00
01
Not Used
(Use as 00 conditions)
19 C5
Increasing Fan
Speed
○
00
01
02
Not Available
Hi Speed 1 (*2)
Hi Speed 2 (*2)
20 C6
Increasing Fan
Speed
○
00
01
Not Available
Available
21 C7
Canceling 3 Minutes
Compressor Guard.
○
00
01
Available
Not Available
22 C8
Thermistor of
Remote Control
Switch
○
00
01
02
Not Available
Control by Indoor
Suction Thermistor
Control by Thermistor
of Remote Control
Switch Control by
Average Value of Indoor
Suction Thermistor and
Thermistor of Remote
Control Switch
23 C9 Not Prepared
-
“- -” Fixed Not Used
24 CA Not Prepared
-
“- -” Fixed Not Used
25 Cb
Selection of Forced
Stoppage Logic
×
00
01
Forced Stoppage Input:
A Contact
Forced Stoppage Input:
B Contact
26 CC Not Prepared
×
00
01
Not Used
(Use as 00 conditions)
27 Cd Not Prepared
○
00
01
Not Used
(Use as 00 conditions)
28 CE Not Prepared
-
00
01
Not Used
(Use as 00 conditions)
29 CF
Change of Louver
Swing Angle
○
00
01
02
Standard (7 Steps)
Draft Prevention
(5 Steps) High Ceiling
(5 Steps) (*3)
30 d1
Power Supply
ON/OFF 1
○
00
01
Not Available
Available
31 d2 Not Prepared
-
“- -” Fixed Not Used
32 d3
Power Supply
ON/OFF 2
○
00
01
Not Available
Available
33 d4
Prevention for
Cooling Discharge
Air Temp. Decrease
○
00
01
Not Available
Available
34 d5
Prevention for
Heating Discharge
Air Temp. Decrease
○
00
01
Not Available
Available
35 d6
Room Temp. Control
for Energy Saving
○
00
01
Not Available
Available
No. Items Optional Function
Individual
Setting
Setting
Condition
Contents
36 d7 Not Prepared
○
00~07
Not Used
(Use as 00 conditions)
37 E1 Ventilation Mode
○
00
01
02
KPI:
Automatic Ventilation
Ventilation by Total
Heat Exchanger
Bypass Ventilation
(No Total Heat
Exchanging)
00
01/02
Econofresh:
Not available
All fresh mode
38 E2
Increasing Supply
Air Volume
○
00
01
Not Available
Available
39 E3 Not Prepared
○
00
01
Not Used
(Use as 00 conditions)
40 E4
Precooling /
Preheating Period
○
00
01
02
KPI:
Standard
30 min.
60 min.
00
01/02
Econofresh:
Standard
CO
2
Sensor
41 E5 Not Prepared
○
00
01
Not Used
(Use as 00 conditions)
42 E6
Indoor Fan
Operation Time After
Cooling Operation
Stoppage
○
00
01
02
Not Available
60 min.
120 min.
43 E7 Not Prepared
-
00
01
Not Used
(Use as 00 conditions)
44 E8
Fan Operation
Control at Heating
Thermo-OFF
○
00
01
Not Available
Available
45 E9 Not Prepared
-
00
01
Not Used
(Use as 00 conditions)
46 EA Not Prepared
○
00
01
02
Not Used
(Use as 00 conditions)
47 Eb
Fan Operation
Control at Cooling
Thermo-OFF
○
00
01
02
Not Available
LOW
SLOW
48 EC
Forced Thermo-ON
Stoppage at Cooling
○
00
01
Not Available
Available
49 Ed Not Prepared
○
00
01
Not Used
(Use as 00 conditions)
50 EE
Automatic Fan
Speed Control
○
00
01
Not Available
Available
51 F1 Not Prepared
-
00~0B Not used
52 F2
Remote Control
Main-Sub Setting
×
00
01
Main
Sub
53 F3 Not prepared
-
00~01 Not used
54 F4 Not prepared
-
00~03 Not used
55 F5 Not prepared
-
19~30 Not used
56 F6 Not prepared
-
17~30 Not used
57 F7 Not prepared
-
00~01 Not used
58 F8
Lock Function for
Operation Mode
Selection
×
00
01
Not Available
Available
(Factory-Setting)
59 F9
Lock Function for
Temperature Setting
×
00
01
Not Available
Available
(Factory-Setting)
60 FA
Lock Function
for Fan Speed
Selection
×
00
01
Not Available
Available
(Factory-Setting)
61 Fb
Lock Function
for Swing Louver
Operation
×
00
01
Not Available
Available
(Factory-Setting)
62 FC
Cooling Lower
Limit for Setting
Temperature (*4)
×
00
01
02
•
•
09
10
Standard
Lower Limit +1ºC
Lower Limit +2ºC
•
•
Lower Limit +9ºC
Lower Limit +10ºC
63 Fd
Heating Upper
Limit for Setting
Temperature (*5)
×
00
01
02
•
•
09
10
Standard
Upper Limit –1ºC
Upper Limit –2ºC
•
•
Upper Limit –9ºC
Upper Limit –10ºC
64 FE Not Prepared
-
00
01
02
Not Used
(Use as 00 condition)
65 FF
Lock Function for
Timer
×
00
01
Not Available
Available (Factory-
setting)
NOTES:
*1: The “02” setting may not be available according to the type of indoor unit.
*2: In case of RPI models, 00: Increasing fan speed 1 (standard),
01: Increasing fan speed 2 (high static pressure), 02: Standard
(low static pressure)
*3: 00: Standard (7-step operation), 01: Draft Prevention (lower 2 steps
cutoff), 02: High ceiling (upper 2 steps cut off)
*4: Applicable to fan, cooling and dry operation modes.
*5: Applicable to heating operation mode.
After at least 3 minutes from the power ON, change the optional setting.
When changing “CF” setting (change of louver swing range), restore the
power supply or allow the louver to make one complete swing fully in the
auto swing mode to apply the optional setting.
The optoinal settings are different according to the indoor and outdoor
unit models. Check to ensure that the unit has the optional setting or not.
Record the setting conditions for each optional setting in the “Setting”
column of the table.