Correct the connector.
Replace the "ion mist unit."
– 248 –
Clean the electrodes.
Is the discharge electrode for ion mist or the
discharge electrode for dust collection covered
with dust, dirt, or other foreign matter?
7.Failure phenomenon: The air purification lamp is blinking (on for 4 seconds, off for 1 second).
[Situation] The air purification lamp is blinking (on for 4 seconds, off for 1 second).
The ion mist unit is not functioning.
The self-diagnosis memory stores "timer lamp blinked 11 times."
[Estimated failure locations] Dirt on the discharge electrode for ion mist and on the discharge
electrode for dust collection
 CN14 connector loose, lead wire break
 High-voltage generator out of order
[Cautions] The self-diagnosis (failure detection) for the ion mist unit is conducted with the timing for the
high-voltage generator to start running when set to "dirt monitoring," "air purification," or
"ion mist."
When touching the electrodes or high-voltage generator, be sure to turn off the power and
guard against electric shocks.
[Diagnosis flow]
Initiating troubleshooting
Ye s
Ye s
Is the CN14 connector loose?
Or is there a lead wire break?