91.5
Vertical positioning
90 in down direction
91.5 in up direction
32
Vertical positioning
90 in down direction
32 in up direction
52.5
Down
Up
52.5 in up direction
90 in down direction
Swing start direction
52.5
Down
(52.5 in up direction)
Up
The air deflector control operation shown below is done when the swing switch is
pressed or when the operation mode is changed.
The air deflector control operation shown below is done when the operation switch
is turned off after the filter sign lamp is lit.
Item
3-way AUTO (Swing)
Specification
Cooling/
dehumidi-
fying
Air
blowing
direction
control
8
The same as cooling
dehumidifying
Other detailed specifications
1. When the room temperature starts to
increase within 3 minutes after thermo
OFF in “cooling” and fan speed “AUTO”,
the fan speed changes L
M
H as
when thermo ON.
2. If “cooling” is selected during “sensor
dehumidification” operation the operation
continues as it is with the thermo ON.
The 3 minutes delay is not started. The
set temperature and fan speed depend
on the remote control signal.
It is same for “cooling” – – – – “sensor
dehumidification”. It is same for “AUTO”
sensor dehumidification cooling “sensor
dehumidification” “cooling”.
3. The filter sign lights after 100 hours
operation of the room fan. The time is
cleared when power switch set to OFF
and ON again.
4. After the failure mode is started (indicator
lamp flickering), rapid mode changing
cannot be done.
5. If the operation is made by the nice
temperature reservation during the sleep
operation, the normal operation
continuously occurs, and for the advance
time, the temperature difference between
the set temperature without sleep shift
and “room temperature” is used.
– 45 –
Operation starts in advance so that the room temperature reaches
the preset value at the set time.
The operation time is obtained as follows depending on the room
temperature when operation starts.
(1) Calculation method of the moved-up time.
Moved-up time (MT) = Moved-up time depending on the temperature
difference (OT) + compensation time (HT).
MT is at least 5 minute if OT is not zero.
Cooling
(MT) 00 ~ 60 min.
(OT) 00 ~ 60 min.
(HT) –60 ~ 60 min.
Obtain OT (moved-up time depending on the temperature difference)
from the table below.
6
“NICE
TEMPERA-
TURE”
reservation
Cooling
Setting temp.
Room temp. Time (min.)
00.00 02.00 00
02.25 05.00 15
05.25 08.00 30
08.25 11.00 45
11.25 60
The preset temperature value shown above does
not include any shift value.
(2) Compensation
1 The “Attained” state is monitored and a “Not attained” check is
done to revise the compensation time (HT).
“Attained” monitor
Continuously monitored during “NICE TEMPERATURE” operation.
(Cooling)
When the room temperature < Set value + compensation shift, it
is regarded to be “attained” and 5 minutes are reduced from the
cooling compensation time.
“Not attained” check
Performed once when the “NICE TEMPERATURE” timer is completed.
(Cooling)
When the room temperature > Set value + compensation shift
+1°C, it is regarded to be “Not attained” and 5 minutes are added
to the cooling compensation time.
If the room temperature is within +1°C from the set value +
compensation shift, compensation is not done.
Item
ON temperature
Thermostat operation (Thermostat relay)
power relay (°C)
Differential (°C)
Low-temperature defrosting
Cooling, sensor
dehumidification
(T1)
16 17.6
24 25.6
32 33.6
0.33
ON (°C) 4.0
Reset (°C) 12.0
Table 2 Sensor operation values
Item RAS-07G4/09G4/14G4
Automatic Yes
Circulator Yes
Operation switching Sensor dehumidification Yes
Cooling Yes
Fan Yes
Temporary switch Yes (automatic)
Service switch Cooling Yes
Nice temperature reservation Yes
Defrosting No
Sleep circuit Yes
Heater operation at the time of sensor dehumidification No
Automatic blowing direction Yes
Filter sign Yes
Wireless mode Cooling
Table 1 Specifications
RAS-07G4/09G4/14G4
Circulator
(When the
operation
switch is
turned off
after the
filter sign
lamp
lights.)