Hitachi RAS-10JH4 - Checking Indoor Unit Electrical Parts; 1. Power Does Not Come On (No Operation)

Hitachi RAS-10JH4
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IPM
INTELLIGENT
POWER MODULE
SELF DIAGNOSIS LAMPS
LD301
LD302
LD303
SERVICE SWITCH
Remove the compressor connector.
If your first attempt
fails, wait 3 minutes
(for the unit to re-
start) and check the
self-diagnosis lamp
status again.
Check outdoor electrical parts.
Check the refrigerating
cycle.
Normal
No
Yes
• Check the drive
circuit (IPM) using
the PRD checker.
• Check the position
sensor circuit.
With the unit set in the operating
state, press the start/stop
button.
Does the unit operate for
approximately 2 seconds (the
LD303 coming on) and then
stop due to a failure of switching
(the lamp blinking 4 times)?
OUTDOOR UNIT
- 81 -