Hitachi RAS-10JH4 - Checking Indoor Unit Electrical Parts; 5. Failure Phenomenon: Ventilation Fan Motor Does Not Operate; Troubleshooting Start

Hitachi RAS-10JH4
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Indoor fan does not operate (others are normal)
Can the fan be stopped by remote
control?
The microcomputer fan PWM
Replace the microcomputer.
.
Replace the fan motor.
.
Replace the microcomputer.
.
Perform final operation check.
Are pulse signals output at
microcomputer pins 15 - 18 when
auto swing is turned on in the fan
mode?
Replace the microcomputer..
Is a voltage over 15 or below 10V
being generated on the 12V line?
No
No
No
No
Perform final operation check.
output (at pin
24
) is 1 - 5V.
Check IC711. If it is normal,
replace the air deflector motor.
Replace IC111.
3. Air deflector does not move (others are normal)
YesYes
Yes
Yes
- 84 -