3
PIPE SIZE SELECTION
PIPING WORK AND REFRIGERANT CHARGE
Ⓖ CH-Box
Type CH-Box Model Branch
Number of connectable
indoor unit per branch
*4
Available combinaon of indoor unit
capacity (HP)
Single
*3
CH-AP160SSX 1 1 - 7
*1
6.0 ≤6.0
CH-AP280SSX 1 1 - 8
*1
10.0 ≤10.0
Mulple
CH-AP04MSSX 4 1 - 6
*2
16.0 ≤6.0 / 1x8.0HP / 1x10.0HP
CH-AP08MSSX 8 1 - 6
*2
30.0 ≤6.0 / 1x8.0HP / 1x10.0HP
CH-AP12MSSX 12 1 - 6
*2
30.0 ≤6.0 / 1x8.0HP / 1x10.0HP
CH-AP16MSSX 16 1 - 6
*2
30.0 ≤6.0 / 1x8.0HP / 1x10.0HP
*1
: When mulple indoor units are connected to the same CH-Box, they are controlled with the same operaon mode.
*2
: The indoor units connected to the same branch of the CH-Box are controlled with the same operaon mode.
*3
: The liquid pipe is not required to connect to the CH-Box.
*4
: In case that the number of connectable indoor unit exceeds four, the high/low pressure gas pipe, gas pipe and liquid
pipe need to increase one size respecvely.
3.2.2 Examples
Total Piping Length
Total length of all liquid pipes (sum)
Maximum Piping Length
Actual length of the liquid pipe from outdoor unit stop
valve or piping connecng kit to the terminal unit.
Example 2 f+h
Piping Length -
Actual length of liquid pipe out of consideraon of local
resistance, such as bent or elbow.
Equivalent Length -
This length is obtained by converng local resistance, such
as bent or elbow, to straight pipe length.
◆ Example 1: Line branch (including main pipe branch)
Indoor
Unit
Indoor
Unit
Outdoor
Unit
A
First Branch
Mul-Kit
a
b
c