43
PMML0628 rev.0 - 05/2023
3
VACUUMING
PIPING WORK AND REFRIGERANT CHARGE
! DANGER
Be sure to use Nitrogen Gas for air-ght test. If other gases such as oxygen gas, acetylene gas or
uorocarbon gas are accidentally used, it may cause an explosion or gas intoxicaon.
3.5.3 Insulaon work
1 Securely insulate high/low pressure and low pressure (for heat recovery system only) gas piping
side and liquid piping side individually. Make sure to insulate the union are nut for the piping
connecon as well.
2 Mount the piping cover equipped with the outdoor unit aer connecng the pipe. Completely
seal the penetraon part at the boom of the pipes with insulaon in order to prevent rain
water from entering the conduit.
3 Cover the gap between the piping cover and pipes with a packing (eld-supplied) aer the
insulaon work is completed.
NOTE
If the gap is not covered, the unit may be damaged if snow, rain water or animals enter the unit.
3.6 Vacuuming
Connect a manifold gauge and vacuum pump to the check joints.
Heat pump system
High/low pressure gas stop valve
Liquid stop valve
Heat recovery system
High/low pressure gas stop valve
Low pressure gas stop valve
Liquid stop valve
3.6.1 Basic Method
If the penetraon of moisture is suspected, perform “Triple Evacuaon Method” that is described
in the next paragraph.
1 Vacuum unl the pressure reaches 500 microns (0.5 mmHg) or Lower for two hours.
2 Aer vacuum pumping work, stop the vacuum pumping and leave the gauge for one hour.
3 Check to ensure that the pressure in the vacuum gauge does not increase.
4 Tighten the caps of check joint according to the specied torque aer the vacuum drying work.
5 If the pressure inside the gauge does not reach 500 microns, it is considered that there is gas
leakage.
6 Check for any gas leakage once again.
7 If no leakage exists, it might be moisture remains inside the pipes. Perform “Triple Evacuaon
Method”.