8.3 BRAZING WORK
! CAUTION
Use nitrogen gas for blowing during pipe brazing. If oxygen, acetylene
or uorocarbon gas is used, it will cause an explosion or poisonous
gas.
A lot of oxidation lm will occur inside of tubes if no nitrogen gas
blowing is performed during brazing work. This lm will be ecked
off after operation and will circulate in the cycle, resulting in clogged
expansion valves, etc. This will cause bad inuence to the compressor.
Use a reducer valve when nitrogen gas blowing is performed during
brazing. The gas pressure should be maintained within 0.03 to
0.05MPa. If a excessively high pressure is applied to a pipe, it will
cause an explosion.
8.4 REFRIGERANT CHARGE
! CAUTION
Do not charge OXYGEN, ACETYLENE, or other ammable and
poisonous gases into the refrigerant because an explosion can occur.
It is recommended that oxygen free nitrogen be charged for these
types of tests cycle when performing a leakage test or an airtight test.
These types of gases are extremely dangerous.
Insulate the unions and are-nuts at the piping connection part
completely.
Insulate the liquid piping completely to avoid a decrease of
performance; if not, it will cause sweating on the surface of the pipe.
Charge refrigerant correctly. Overcharging or insufcient charging
could cause a compressor failure.
Check for refrigerant leakage in detail. If a large refrigerant leakage
occurred, it would cause difculty with breathing or harmful gases
would occur if a re were being used in the room.
If the are nut is tigthened too hard, the are nut may crack after a
long time and cause refrigerant leakage.
8.5 REFRIGERANT CHARGING QUANTITY


Outdoor unit refrigerant
charge (kg)
Chargeless length (m)
Additional refrigerant
charge (P) (g/m)
Max additional charge
(kg)
RAS-2WHVRP 

 
RAS-2.5WHVRP   
RAS-3WHVRP 




1 
2 
! CAUTION
When charging refrigerant accurately measure refrigerant to be charged.
Overcharging or undercharging of refrigerant can cause compressor trouble.
Refer to indoor unit installation manual for refrigerant charge and minimum oor requirements.
8.6 CAUTION OF THE PRESSURE BY CHECK JOINT





Cooling
operation
Heating
operation
  



? NOTE
Be careful that refrigerant and oil do not splash to the electrical parts at
removing the charge hoses.



PMML0509 rev.0 - 02/2019
