4 Electrical wiring
99
SMGB0087 rev.0 - 12/2013
4
MODEL Z
max
(Ω) MODEL Z
max
(Ω)
RAS-2HVNP1 -
RAS-2.5HVNP1 -
RAS-3HVNP1E - RAS-3HVNC1 0.42
RAS-4HVNP1E - RAS-4HVNC1E -
RAS-5HVNP1E - RAS-5HVNC1E -
RAS-6HVNP1E - RAS-6HVNC1E -
RAS-4HNP1E - RAS-4HNC1E -
RAS-5HNP1E - RAS-5HNC1E -
RAS-6HNP1E - RAS-6HNC1E -
RAS-8HNPE - RAS-8HNCE -
RAS-10HNPE - RAS-10HNCE -
RAS-12HNP - RAS-12HNC -
3 Harmonics situation of each model regarding IEC 61000-3-2 and IEC 61000-3-12 is as follows:
MODELSSITUATIONREGARDINGIEC61000-3-2andIEC61000-3-12 MODEL
Equipment complying with IEC 61000-3-2
N O T E
(*) professional use
RAS-2HVNP1
RAS-2.5HVNP1
RAS-3HVNC1
RAS-4HNP1E (*)
RAS-5HNP1E (*)
RAS-6HNP1E (*)
RAS-4HNC1E (*)
RAS-5HNC1E (*)
RAS-6HNC1E (*)
Equipment complying with IEC 61000-3-12
RAS-3HVNP1E
RAS-4HVNP1E
RAS-5HVNP1E
RAS-6HVNP1E
RAS-4HVNC1E
RAS-5HVNC1E
RAS-6HVNC1E
Installation restrictions may be applied by supply authorities in relation to harmonics
MODEL
RAS-8HNPE
RAS-8HNCE
RAS-10HNPE
RAS-10HNCE
RAS-12HNP
RAS-12HNC
4 Check to ensure that the power supply voltage is within +/-10% of the rated voltage.
5 Check to ensure that power supply has an impedance low enough to warranty not reduce the starting voltage more
than 85% of the rated voltage.
6 Check to ensure that the ground wire is connected.
7 Connect a fuse or circuit breaker of specied capacity.