10 Servicing
378
SMGB0087 rev.0 - 12/2013
10.4.8 Removing the High pressure switch and Pressure switch for control
1 Remove the service cover and the bottom service cover following “10.4.1Removingservicecover”, and “10.4.4Remo-
vingthebottomservicecoverandrearcover”.
2 Collect the refrigerant from the check joint according to “10.4.7Removingthecompressor”in this chapter.
High pressure switch and pressure switch for control
1 Disconnect the Faston Terminals of High Pressure Switch and Pressure sensor for PD control.
2 Remove the high pressure switch and the pressure switch for control from the brazed part of discharge piping.
N O T E
Theprocedure(1)isnotrequiredwhenremovingthepressuresensorforPDcontrol.However,checktoensurethatthe
connector(CN100)onO.U.PCB1isdisconnected.
Low pressure switch
1 Disconnect the Faston Terminals of Low Pressure Switch.
2 Remove the low pressure switch from the brazed part of suction piping.
Discharge Pipe
Brazing Part
Brazing Part
Brazing Part
Low Pressure Switch (PSL)
Suction Pipe
High Pressure Switch (PSH)
Pressure Sensor for PD Control
to DRM1 and SC terminals.
or transmission wiring
Do not connect power supply
17E26270A
CAUTION
SCAS4755 DRM1
PCN1
TR1
IC1