Although the wireless controller is used for the wall type indoor unit with the built-in receiver part, you can check the alarm
code by connecting the PC-ART.
N O T E
The unit does not operate by pressing the operation
switch.
The above function is available only when the alarm
occurs.
The PCB check by means of the remote control switch is
not available.
The indication is the data when you are connecting PC.ART.
The indication is not the data before the alarm occurs.
Contents of the Check mode 1
The next indication is shown if you press the part "▲of the TEMP switch.
If you press the part "▼ of the TEMP switch, the previous indication is shown.
Temperature indication
1
Indoor unit temp.
setting (°C)
b1 22
2
Indoor unit air inlet
temp. at thermistor
(°C)
b2 20
3
Indoor unit discharge
air temp. at thermistor
(°C)
b3 55
4
Indoor unit heat
exchanger liquid pipe
temp °C
b4 20
5
Temperature at remote
sensor (°C)
b5 25
6
Outdoor unit ambient
temp. (°C)
b6 10
7
Indoor unit heat
exchanger gas pipe
temp. (°C)
b7 25
8
Outdoor unit
evaporating temp.
during heating (°C)
b8 02
9 Control information
b9 
10
Discharge gas temp.
at the top of the comp.
chamber (°C)
b 41
11
Thermo temp. of the
remote control switch
bb 23
(Thermistor is open-circuited
or PCB is defective)
(Thermistor is short-circuited
or PCB is defective)
Indication of the category code
Indication of the temperature, etc
(Ex.) During the operaton of several compressors, the average
temperature of two compressors is indicated.
If the temperature is higher than 126 ºC, “126
This indicates the internal information for the remote control switch
This is indicated only when a remote sensor is connected.
The indicator "--" is normally displayed.
RPK series cannot connect a remote sensor.
Therefore, the indicator is "--".
During the transient periods such as starting time and other, the
indicators "" or "00" may be displayed for a limited time.
Normal
Abormal
... Temperature displayed

129
FF
255
127
(Temp. for top of comp.)
(Temp. for top of comp.)
or
or
or
Refer to section 8.3.1 “Self-Checking
Procedure of PCB by means of the Remote
Control Switch"
8 Troubleshooting
285
SMGB0060 rev. 1- 12/2010