TOOL: Multimeter.
Insert screwdriver into to rotate indoor fan motor slowly for 1 revolution or over, and measure
voltage “YELLOW” and “GND” on motor. The voltage repeat 0V DC and 5V DC.
Notes:
Please dont hold motor by lead wires.
Please dont plug IN/OUT the motor connecter while power ON.
Please dont drop hurl or dump motor against hard material. Malfunction may not be observed at early
stage after such shock. But it may be found later, this type of mishandling void our warranty.
36
3.CHECKING COMPONENTS