3 Piping work and
refrigerant charge
96
SMGB0087 rev.0 - 12/2013
3.7 Drainpiping
3.7.1 Drain discharging boss
When the base of the outdoor unit is temporarily utilized as a drain receiver and the drain water in it is discharged, this drain
boss is utilized to connect the drain piping.
Model ApplicableModel
DBS-12L
RAS-(2/2.5)HVNP1
RAS-3HVNC1
DBS-26
RAS-3HVNP1E
RAS-(4-6)H(V)N(P/C)1E
RAS-(8-10)HN(P/C)E
RAS-12HN(P/C)
Connecting procedure
1 Insert the plastic cap into the drain boss up to the extruded portions.
2 Insert the boss into the unit base up to the extruded portions.
3 Size of the drain boss is:
- For DBS-12L: 15 mm (O.D.)
- For DBS-26: 32 mm (O.D.)
4 A drain pipe should be eld-supplied.
N O T E
• Donotusethisdrainbosssetinacoldarea,becausethedrainwatermayfreeze.
• Thisdrainbossisnotsufcienttocollectallthedrainwater.Ifcollectingdrainwateriscompletelyrequired,providea
drain-panthatisbiggerthantheunitbaseandinstallitundertheunitwithdrainage.
RAS-(2-2.5)HVNP/RAS-3HVNC
RAS-3HVNPE/RAS-(4-6)H(V)N(P/C)E/
RAS-(8-10)HN(P/C)E/RAS-12HN(P/C)
Drain pipe
Plastic cap
Plastic cap
Drain hole
100 mm
Plastic cap
Drain hole
Push Push
≥ O.D. ∅ 16 mm
Rubber cap
Drain boss
Extruded portion
Drain pipe
Drain pipe
Drain hole
of base