4 Electrical wiring
109
SMGB0087 rev.0 - 12/2013
4
4.4.2  Wire size
Connection wiring
Recommended minimum sizes for eld provided wires:
Model Powersupply
Powersourcecablesize Transmittingcablesize
EN60335-1 EN60335-1
All Indoor Units 1~ 230V 50HZ 0.75 mm² 0.75 mm²
IVXPremiumSeries
RAS-2HVNP1
1~ 230V 50HZ
2.5 mm²
0.75 mm²
RAS-2.5HVNP1
4.0 mm
2
RAS-3HVNP1E
RAS-4HVNP1E
6.0 mm
2
RAS-5HVNP1E
RAS-6HVNPE
RAS-4HNP1E
3N~ 400V 50Hz
2.5 mm
2
RAS-5HNP1E
RAS-6HNP1E
RAS-8HNPE
6.0 mm
2
RAS-10HNPE
RAS-12HNP
IVXStandardSeries
RAS-3HVNC1
1~ 230V 50HZ
4.0 mm
2
0.75 mm²
RAS-4HVNC1E
6.0 mm
2
RAS-5HVNC1E
RAS-6HVNC1E
RAS-4HNC1E
3N~ 400V 50Hz
4.0 mm
2
RAS-5HNC1E
RAS-6HNC1E
RAS-8HNCE
6.0 mm
2
RAS-10HNCE
RAS-12HNC
N O T E
• Followlocalcodesandregulationswhenselectingeldwires,circuitbreakersandearthleakagebreakers
• Usethewireswhicharenotlighterthantheordinarypolychloroprenesheathedexiblecord(codedesignationH05RN-F)