4 Electrical wiring
110
SMGB0087 rev.0 - 12/2013
IVX Premium series
Outdoorunit MC(A) CB(A) ELB
RAS-2HVNP1 12.0 16
2/40/30
RAS-2.5HVNP1 14.0 20
RAS-3HVNP1E 19.0 20
RAS-4HVNP1E 28.0 32
RAS-5HVNP1E 28.0 32
RAS-6HVNPE 28.0 32
RAS-4HNP1E 11.5 15
4/40/30
RAS-5HNP1E 11.5 15
RAS-6HNP1E 13.5 15
RAS-8HNPE 24.0 30
RAS-10HNPE 24.0 30
RAS-12HNP 24.3 30
IVX Standard series
Outdoorunit MC(A) CB(A) ELB
RAS-3HVNC1 16.0 20
2/40/30
RAS-4HVNC1E 28.0 32
RAS-5HVNC1E 28.0 32
RAS-6HVNC1E 28.0 32
RAS-4HNC1E 15.0 20
4/40/30
RAS-5HNC1E 15.0 20
RAS-6HNC1E 15.0 20
RAS-8HNCE 24.0 30
RAS-10HNCE 24.0 30
RAS-12HNC 24.3 30
Main switch protection
Select the main switches in according to the next table:
Model Powersupply Max.current(A) CB(A) ELB(no.poles/A/mA)
All Indoor Units 1~ 230V 50Hz 5.0 6 2/40/30
ELB: Earth switch; CB: Circuit breaker