6 Optional functions
169
SMGB0087 rev.0 - 12/2013
6
N O T E
• Thisisanauxiliaryfunctiontoprotecttheunitfromsnow.Insnowyregions,makesuretoprotecttheunitwithasnow-
preventionroof,fenceorsnow-preventionhood(Field-Supplied),etc..Otherwise,abnormalvibrationsduetoimbalan-
cedpropellerfanwillbecaused.
• Ifthefanmotororfancontrollerfailduringtheintermittentoperationofoutdoorfanmotor,stopalltheoutdoorfanmotor
tosuspendtheoperation.Checkthealarmcodeanddealproperlywiththefailurenexttimethecompressorisoperated.
• WhensettingthesnowsensorswitchforIntermittentOperationofOutdoorFanMotor,makesurethatthecontinuous
operatingtimeis30secondsormore.Alsotheintermittentoperationofoutdoorfanmotorintervalsshallbeatleast10
minutes.Otherwise,malfunctionoftheoutdoorfanmotorswillbecausedbyfrequentstart/stop.
D A N G E R
• Becauseofthissetting,theoutdoorfancanoperateevenwhiletheoutdoorunit(compressor)stops.
• Displayanoticetothateffectonareadilyvisiblepartoftheunitbody,inordertoavoidinjuriescausedbyan
unintendedoutdoorfanoperation.
d. Forcedstoppage(4/5)
(4)-RAS-(2.0-2.5)HVP1 / RAS-3HVNC1
(5)-RAS-3AVHNP1E / RAS-(4-12)H(V)N(P/C)(1)(E)
This is an input function that turns on when the switch receives a signal that causes the compressor and the fan motor of
the indoor unit to stop; stoppage code d1=10 displays on a remote-controlled when this option turns on. If the switch of this
function is disconnected it becomes available again.
Connect the cabling and use the materials as shown in”6.1.1Availableports”.
e. Currentcontroldemand(5/6/7/8/9/10)
(5,6,7)-RAS-(2.0-2.5)HVP1 / RAS-3HVNC1
(6,7,8,9)-RAS-(3.0-6.0)H(V)NP1E / RAS-(8.0-12.0)HN(C/P)(E)
(6,7,8,9,10)-RAS-(4.0-6.0)H(V)C1E
This is an input function that turns on when it detects that the frequency of the compressor reaches 60%, 80% or 100% for
RAS-(2.0-2.5)HVP1 / RAS-3HVNC1, 60%, 70%, 80% or 100% for RAS-(3.0-6.0)H(V)NP1E / RAS-(8.0-12.0)HN(C/P)(E)
and 40%,60%, 70%, 80% or 100% for RAS-(4.0-6.0)H(V)C1E
The frequency of the compressor is determined when the maximum current reaches the established limit.
Connect the cabling and use the materials as shown in “6.1.1Availableports”.
If the running current of the outdoor unit exceeds the maximum limit, the unit changes to the thermo-OFF condition. Stop-
page cause code “10” will appear. When the input terminal is opened during the demand current control, the control of the
input terminal is reset.
N O T E
Iftheinputterminalsareopenedbyatimer,etc.on-siteandthedemandcontrol(ON/OFF)issetwithonlytimeconditions,
itisrecommendedtosetthetimeaccordingtotheload,nottheconstantsettingtimeallthroughtheyear.Theminimum
setintervalfordemandorforcedstoppageshouldbe30minutesinconsiderationofthecompressor’sstart/stopfrequency
andenergy-saving.